Extruded Aluminum Louvers

Free Area Based on 48x48 Unit Water Penetration Ratings Based on 48x48 Unit Wind Driven Rain Ratings Based on 39x39 Unit Certified Ratings Program Building Code Listings Product Sheet CSI Specification Installation Instructions Revit Files
Model Frame Depth Blade Angle Type Blade Style SQFT Percent Velocity (fpm) Air Volume (cfm) Pressure Loss (inwg) Wind Class Effectiveness Ratio Rainfall Rate Wind Speed Core Velocity(fpm) Airflow(cfm) AMCA Florida Building Code Miami Dade Certified
EBV-145 1.5" 45 Brick Vent J - - - - - N/A - - - - - - - - PDF Doc RFA
EBV-445 4" 45 Brick Vent J - - - - - N/A - - - - - - - - PDF Doc RFA
ECD-445 4" 45 Wind-Driven Rain Drainable Chevron 6.9 43% 1,250 8,585 0.31 A 99% 3 in/hr 29 mph 423 6,768 Air, Water, Wind - - PDF Doc PDF RFA
ECD-545 5" 45 Wind-Driven Rain Drainable Chevron 7.4 46% 1,250 9,250 0.22 A 100% 3 in/hr 29 mph 668 7,196 Air, Water, Wind - PDF Doc PDF RFA
ECD-545 5" 45 Wind-Driven Rain Drainable Chevron 7.4 46% 1,250 9,250 0.22 B 97.90% 8 in/hr 50 mph 676 7,276 Air, Water, Wind - PDF Doc PDF RFA
ECD-545-MD 5" 45 Miami Dade Drainable Chevron 7.4 46% 1,250 9,250 0.22 A 100% 3 in/hr 29 mph 668 9,419 Air, Water, Wind - PDF Doc PDF RFA
ECD-545-MD 5" 45 Miami Dade Drainable Chevron 7.4 46% 1,250 9,250 0.22 B 97.90% 8 in/hr 50 mph 676 9,532 Air, Water, Wind - PDF Doc PDF RFA
ECD-635 6" 35 Wind-Driven Rain Drainable Chevron 8.6 54% 1,217 10,508 0.29 B 96.60% 3 in/hr 29 mph 441 6,372 Air, Water, Wind - - PDF Doc PDF RFA
ECD-745 7" 45 Wind-Driven Rain Drainable Chevron 8.4 53% 1,197 10,018 0.5 A 99.90% 3 in/hr 29 mph 493 7,244 Air, Water, Wind - - PDF Doc PDF RFA
ECV-445 4" 45 Wind-Driven Rain Vertical Chevron 5.7 36% 1,250 7,125 0.76 A 99.80% 3 in/hr 29 mph 688 4,211 Air, Wind - - PDF Doc PDF RFA
ECV-545 5" 45 Wind-Driven Rain Vertical 6.7 42% 1,250 8,375 0.25 A 99.60% 8 in/hr 50 mph 881 9,845 Air, Water, Wind - - PDF Doc PDF RFA
ECV-545 5" 45 Wind-Driven Rain Vertical 6.7 42% 1,250 8,375 0.25 A 99.90% 3 in/hr 29 mph 683 7,356 Air, Water, Wind - - PDF Doc PDF RFA
ECV-645 6" 45 Wind-Driven Rain Vertical Chevron 7.4 46% 1,250 9,250 0.15 A 100% 8 in/hr 50 mph 965 10,390 Wind - PDF Doc PDF RFA
EDD-445 4" 45 Drainable Dual Drainable 8.1 50% 1,026 8,311 0.16 N/A - - - - - Air, Water - - PDF Doc PDF RFA
EDD-637 6" 37-1/2 Drainable Dual Drainable 9.2 58% 1,113 10,242 0.15 N/A - - - - - Air, Water - - PDF Doc PDF RFA
EFD-245 2" 45 Drainable D 6.8 43% 955 6,494 0.14 N/A - - - - - - - - PDF Doc PDF RFA
EFD-435 4" 35 Drainable D 9.3 58% 966 8,984 0.12 N/A - - - - - Air, Water - - PDF Doc PDF RFA
EFD-437 4" 37-1/2 Drainable D 9.3 58% 903 8,398 0.13 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFD-445 4" 45 Drainable D 7.5 47% 990 7,425 0.14 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFD-637 6" 37-1/2 Drainable D 9.2 58% 1113 10,242 0.15 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFD-637-MD 6" 37-1/2 Miami Dade D 9.3 58% 1097 10,191 0.17 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFD-645 6" 45 Drainable D 8.8 55% 1,050 9,240 0.15 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFJ-245 2" 45 Thinline J 7.5 47% 583 4,373 0.06 N/A - - - - - - - - PDF Doc PDF RFA
EFJ-430 4" 30 Non-Drainable J 9.1 57% 889 8,090 0.09 N/A - - - - - - - - PDF Doc PDF RFA
EFJ-437 4" 37-1/2 Non-Drainable J 9.1 57% 721 6,547 0.07 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFJ-437-HP 4" 37-1/2 Drainable Head J 9 56% 912 8,220 0.14 N/A - - - - - Air, Water - - PDF Doc PDF RFA
EFJ-445 4" 45 Non-Drainable J 8 50% 689 5,549 0.08 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFJ-637-HP 6" 37-1/2 Drainable Head J 9 56% 915 8,226 0.12 N/A - - - - - - - - PDF Doc PDF RFA
EFJ-645 6" 45 Non-Drainable J 8 50% 800 6,416 0.1 N/A - - - - - - - - PDF Doc PDF RFA
EFJ-745 7" 45 Wind-Driven Rain J (Face) Vertical
C (Rear)
7 44% 1,250 8,755 0.47 A 99% 3 in/hr 29 mph 670 7,211 Air,Wind - - PDF Doc PDF RFA
EFK-430 4" 30 Non-Drainable K 9.1 57% 889 8,090 0.09 N/A - - - - - - - - PDF Doc PDF RFA
EFK-437 4" 37-1/2 Non-Drainable K 9.1 57% 721 6,547 0.07 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFK-445 4" 45 Non-Drainable K 8 50% 689 5,549 0.08 N/A - - - - - Air, Water - PDF Doc PDF RFA
EFK-637 6" 37-1/2 Non-Drainable K 8 50% 832 6,673 0.05 N/A - - - - - - - - PDF Doc PDF RFA
EFY-245 2" 45 Sightproof Inverted Y 6.1 38% 383 2,336 0.06 N/A - - - - - - - - PDF Doc PDF RFA
EFY-445 4" 45 Sightproof Inverted Y 6.2 39% 745 4,589 0.18 N/A - - - - - - - - PDF Doc PDF RFA
ERD-645 6" 45 Recessed Mullion D 8.1 51% 990 8,059 0.11 N/A - - - - - - - - PDF Doc PDF RFA
EVS-422 4" 22 Sand Vertical Chevron 2.5 16% 1,250 3,125 1 N/A - - - - - - - - PDF Doc PDF RFA